UL 1567:1998 pdf download

12-29-2022 comment

UL 1567:1998 pdf download Receptacles and Switches Intended for Use with Aluminum Wire .
1 Scope
1.1 These requirements cover wire binding screw terminals of receptacles and switches rated 15 or 20 Aintended for use with solid conductor aluminum building wire, and that require direct connection of wiringconductor(s) to the binding head screw terminal(s) prior to insertion of the device in an outlet box.
1.2 These performance requirements for wire binding screw terminals are in addition to the requirementsfor the products covered by the Standard for Attachment Plugs and Receptacles, UL 498, and theStandard for General-Use Snap Switches,UL 20.
1.3 A product that contains features, characteristics, components, materials, or systems new or differentfrom those covered by the requirements in this Standard, and that involves a risk of fire, electric shockor injury to persons, shall be evaluated using the appropriate additonal component and end-productrequirements as determined necessary to maintain the acceptable level of safety as originally anticipatedby the intent of this Standard. A product whose features, characteristics, components, materials,osystems conflict with specific requirements or provisions of this Standard cannot be judged to complwith this Standard. Where considered appropriate, revision of requirements shall be proposed andadopted in contormance with the methods emploved for development revision, and implementation othis Standard.
*1.3 revised November 30,1998*
2 Components
2.1 Except as indicated in 2.2, a component of a product covered by this Standard shall comply withthe requirements for that component.
“2.1 added November 30,1998
2.2 A component need not comply with a specific requirement that:
a) Involves a feature or characteristic not needed in the application of the component in theproduct covered by this Standard, or
b) ls superseded by a requirement in this Standard.
*2.2 revised November 30, 1998*2.3 A component shall be used in accordance with its recognized rating established for the intendedconditions of use.
*23 added November 30,1998“
2.4Specific components are recognized as being incomplete in construction features or restricted inperformance capabilities. Such components are intended for use only under limited conditions, such ascertain temperatures not exceeding specified limits and shall be restricted to use only under thosespecific conditions for which they have been recognized.
“2.4 added November 30,1998
3 Units of Measurement
3.1 When a value for measurement is followed by a value in other units in parentheses, the first statedvalue is the requirement.
4References
4.1 Any undated reference to a code or standard appearing in the requirements of this Standard shallbe interpreted as referring to the latest edition of that code or standard.
PERFORMANCE
5General
5.1 Test Wire Size – Products rated 15 or 20 A shall be investigated for use with No. 12 (3.3 mm?) andNo, 10 AWG (5.3 mm’) aluminum conductors when they are intended for use on branch circuitsprotected by overcurrent protection rated either 15 or 20 A in accordance with the National ElectricaCode (NEC) ANSI/NFPA-70. Products rated 20 A shall be investigated for use with No. 10 AWG wireProducts rated 15 A that are not intended for use on a 20-A branch circuit shall be investigated with No12 AWG wire.

                                           Related Information                                             Download
PS:Thank you for your support!
UL 583:2002 pdf download UL Standards

UL 583:2002 pdf download

UL 583:2002 pdf download Request for Comments on Proposed Requirements for the Proposed First Edition of the Standard for Electric-Battery-Powered Cleaning Machines, UL 2317; PROPOSED EFFECTIVE DATE 1 Scope 1.1 These requirements cover electric-battery-powered cleaning machines such...
Read More
UL 1042:2002 pdf download UL Standards

UL 1042:2002 pdf download