IEEE 18-2002 pdf download IEEE Standard for Shunt Power Capacitors
6.7 Information to be provided with capacitor
6.7.1 Nameplate marking
Each (power) capacitor shall be provided with a permanent nameplate that includes, but is not limited to, the following information:
a) Name of manufacturer.
b) Unique serial number.
c) Manufacturer’s type, model, style, or catalog number.
d) Year of manufacture.
e) Rated reactive power.
f) Rated voltage, rms.
g) Number of phases.
h) Rated frequency.
i) BIL (if applicable). For capacitors having bushings with two different BIL ratings, the nameplate shall show both BIL ratings, e.g. 150/95 kV BIL.
j) Flammability classification and volume of insulating fluid.
k) Statement that capacitor contains an internal discharge device.
6.7.2 Information to be supplied with internally fused capacitors or capacitor units for fuseless capacitor equipment
The information in 6.7.2.1 and 6.7.2.2 shall be provided as follows:
a) On the capacitor unit nameplate, and/or
b) On the capacitor equipment nameplate, and/or
c) On the instructions provided with the capacitor(s).
6.7.2.1 Internally fused capacitors
a) The number of series groups between the terminals and the number of parallel elements in each series group.
b) Maximum number of individual fuse operations in one series group of the capacitor unit before the capacitor unit must be removed from service, when the capacitor unit is operated at 110% of rated voltage across its terminals. (Overvoltages on unfaulted capacitor units also need to be considered in the setting of the protective relays.)
6.7.2.2 Capacitor units for fuseless capacitor equipment
The number of series groups between the terminals of the capacitor unit.
6.7.3 Non-PCB impregnant identification
Additional marking (decal or stick-on label) shall be visible from the ground. A blue marking shall be used to designate non-polychlorinated biphenyl (non-PCB) liquid.