EN 303-6-2019 pdf download

07-07-2021 comment

EN 303-6-2019 pdf download.Heating boilers – Part 6: Heating boilers with forced draught burners – Specific requirements for the domestic hot water operation and energy performance of water heaters and combination boilers with atomizing oil burners of nominal heat input not exceeding 70 kW.
The domestic water circuit is subjected to a pressure of 1,5 times the maximum pressure given on the
data plate for 10 mm.
It is checked that the requirements of 5.2.1.1 are met.
6.2.1.2 Overheating of the domestic hot water by the central heating circuit
The central heating circuit thermostat is set at its maximum position.
The appliance operates continuously for one hour at the nominal heat input in the central heating mode, without drawing domestic hot water. A draw off at the specific rate D is then carried out and the requirement of 5.2.1.2 is checked.
6.2.1.3 Failure of the domestic hot water temperature control device
To check the requirements of 5.2.1.3, the draw off domestic water rate is progressively reduced after having put out of action the adjusting control of the domestic water circuit, in accordance with the test methods relating to the limit thermostat or the temperature limiter with the boiler operating at its maximum heat input.
6.2.2 Instantaneous type
6.2.2.1 Maximum temperature of the domestic hot water
The boiler is operated at the nominal domestic hot water heat input with a domestic water supply pressure of 2 bar.
Starting with this 2 bar supply pressure, the pressure is progressively reduced until the burner is extinguished. The water outlet temperature is measured continuously with a low inertia thermometer. The maximum temperature is measured and shall satisfy the requirements of 5.2.2.1.
6.2.2.2 Overheating of the domestic hot water
The boiler is operated at the nominal domestic hot water heat input, where appropriate. The water rate and any water temperature control are adjusted to obtain the maximum water temperature at the nominal domestic hot water heat input.
After the boiler has operated for 10 mm, the hot water delivery tap is turned off quickly. After 10 s the tap is turned on quickly and the highest temperature at the centre of the flow, as close as possible to the boiler outlet, is measured by means of a low inertia thermometer. The boiler remains in operation until it has again reached its steady-state condition, The same measurements are made during similar operating cycles, but with the time that the draw off is stopped increased each time by 10 s, until the maximum temperature is obtained.
It is checked that the requirement of 5.2.2.2 is met.
6.2.3 Storage type
62.3.1 Maximum temperature of the domestic hot water
The boiler is operated at the nominal domestic hot water heat input with the domestic water thermostat at its maximum position. A draw off is carried out after a shut-down of the burner. The maximum temperature measured shall meet the requirement of 5.2.3.1.
6.2.3.2 OverheatIng of the domestic hot water
The test starts after the tank or the thermal store has reached temperature and after the burner has been shut down a second time by the controls. Water is drawn off several times at a rate corresponding to 5 % of the water capacity of the tank, in litres per minute.
On each occasion, water is drawn until the burner ignites and at least 95 % of the nominal domestic hot water heat input is obtained. The next draw off then takes place immediately after the burner shuts down, and so on until the maximum temperature is obtained.
For modulating burners or multi-stage burners, the following draw off takes place when the fuel rate has decreased at least to 50 % of the maximum domestic hot water heat input reached.
At the start of each draw off, the temperature of the delivered water is measured and it is checked that the requirement of 5.2.3.2 is mel
6.2.3.3 Temperature of the domestic hot water
Where applicable, the adjuster is placed in the position stated by the manufacturer. After a controlled shutdown of the boiler, a draw off is carried out for 10 mm at a rate equivalent to S % of the water capacity of the tank per minute or at the minimum rate stated by the manufacturer which allows burner ignition if this is greater than 5 % of the capacity of the tank per minute.EN 303-6-2019 pdf download.

                                           Related Information                                             Download
PS:Thank you for your support!
EN 152-1:1988 pdf download EN Standards

EN 152-1:1988 pdf download

EN 152-1:1988 pdf download,Test methods for wood preservatives;Laboratory method for determining the preventive effectivenessof a preservative treatment against blue stain in service Part 1:Brushing procedure. The test method described in this European Standard is a laboratory method...
Read More
EN 74:1988 pdf download EN Standards

EN 74:1988 pdf download

EN 74:1988 pdf download.Cooplers,loose spigots and base-plates for use in working scaffolds and falsework made of steel tubes; Requirements and test procedures Key words Steel tubes,Scaffolding,Fasteners,Pipe fittings,Centring pins,Supports,Equipment specifications,Inspection methods,Sampling,Mechanical tests.
Read More
EN 50061:1988 pdf download EN Standards

EN 50061:1988 pdf download

EN 50061:1988 pdf download,Safety of implantable cardiac pacemakers. This standard EN 50061:1988 specifies safety and other requirementsexclusively for all types of wholly implantable cardiac PACEMAKERS. This standard EN 50061:1988 also establishes basic terminology and definitions and includes...
Read More

LEAVE A REPLY

Anonymous netizen Fill in information