EN 17255-2-2020 pdf download.Stationary source emissions – Data acquisition and handling systems – Part 2: Specification of requirements on data acquisition and handling systems.
6.2.2.2 Analog communication
A/D converters of analogue communication interfaces shall meet the following requirements:
— resolution shall be at least 12 bit but a resolution of 16 bit is recommended;
— relative accuracy shall be better than ± 0,1 % of the range (in case of multiple ranges, it refers to every range);
— input range shall be able to handle live zero signals, e.g. analogue signals at 4 mA or 2 V. The DAI-IS shall be able to receive hard-wired status signals.
6.2.2.3 Digital communication
Digital communication interfaces shall handle the transmission of input data and associated status information to the DAHS.
Digital communication interfaces shall provide the following functionality:
— a documented communication protocol providing data integrity, e.g. Modbus, PROFIBUS, OPC; NOTE I Standard communication protocols provide measures for data integrity.
— uniqueaddressingofinput data sources, e.g. measuringsystem.within asystem containingthe DAHS; NOTE 2 Several measurands can be related to one address.
— unique allocation of all measurands and all status signals to the address of the input data source;
— transmission of the measured signals with a resolution of the measured signals of 32 bit floating. point number according to IEEE 754;
— control of applying zero and reference materials to the AMS, if QAL3 is controlled by the DAHS;
— status information associated to the measured signals including at least identification of valid measured signal, maintenance of the measuring system and malfunction of the measuring system;
NOTE 3 The distinction between the status of the measured signal and of the measuring system allows in case of multiple-component measuring systems the use of the remaining measured components, when one measured component is disturbed.
— ability to test the digital communication between the DAHS and each input data source.
The manufacturer shall specify in a datasheet for each input data source the interface specific data and procedures to access the data.
The DAHS shall provide the capability for manual data input for other data, e.g. QAL3 data, QAL3 correction factors or eventlog entries.
Whenever this data are entered either by keypad or other data media, the DAI-IS shall record the user ID and changes made into the event log (see 6Zd). Manual input shall not overwrite automatically transmitted data.
6.2.4 Remote data logger unit
Remote data logger units as part of the DAHS can be used to temporarily store raw data to avoid loss of data if the DAHS processing unit is ofiline. Data shall be transferred between the remote data loggers and the DAHS processing unit by a secure communication protocol.
6.3 Input data processing
6.3.1 Validity of input data
The validity of all input data shall be verified.
The DAKS shall be able to identify failure for analogue interfaces by loss of connection e.g. by broken circuit, or for digital interfaces by loss of digital communication. Input data obtained during these periods shall be flagged as invalid.
The DAHS shall check that the input data values are within the specified measurement range. Input data values outside the specified measurement range shall be tagged as ‘out of range’.
NOTE The AMS is considered to be ‘out of range’ for the time period in which the measured values are above the upper or below the lower limit of the measurement range of the AMS. In this case, the measured values can be used for further calculations, unless stipulated otherwise, for example by legislation.
AMS raw data shall be tagged valid if the AMS input data are valid and the AMS is in a measuring mode, e.g. not in test, service, functional test, failure or similar. Otherwise the AMS raw data shall be invalid.
6.3.2 First level data (FLD)
The DAHS shall be able to form and handle FLD in accordance with the specifications of EN 17255-1.
FLD shall be stored In accordance with the requirements of4.
If FLD are determined from scaled AMS raw data, all the scaling factors shall be retrievable. NOTE Scaling to units includes e.g. a conversion from milliamps (mA) to milligram per cubic meter (mg/rn3). or from Volt (V) to Kelvin (K).
The parameters used for determining the plant status from input data shall be retrievable.EN 17255-2-2020 pdf download.

                                           Related Information                                             Download
PS:Thank you for your support!
EN 152-1:1988 pdf download EN Standards

EN 152-1:1988 pdf download

EN 152-1:1988 pdf download,Test methods for wood preservatives;Laboratory method for determining the preventive effectivenessof a preservative treatment against blue stain in service Part 1:Brushing procedure. The test method described in this European Standard is a laboratory method...
Read More
EN 74:1988 pdf download EN Standards

EN 74:1988 pdf download

EN 74:1988 pdf download.Cooplers,loose spigots and base-plates for use in working scaffolds and falsework made of steel tubes; Requirements and test procedures Key words Steel tubes,Scaffolding,Fasteners,Pipe fittings,Centring pins,Supports,Equipment specifications,Inspection methods,Sampling,Mechanical tests.
Read More
EN 50061:1988 pdf download EN Standards

EN 50061:1988 pdf download

EN 50061:1988 pdf download,Safety of implantable cardiac pacemakers. This standard EN 50061:1988 specifies safety and other requirementsexclusively for all types of wholly implantable cardiac PACEMAKERS. This standard EN 50061:1988 also establishes basic terminology and definitions and includes...
Read More

LEAVE A REPLY

Anonymous netizen Fill in information