BS/EN 50173-5-2018 pdf download.Information technology – Generic cabling systems Part 5 : Data centre spaces.
requirements of this document. For dated references, only the edition cited applies. For undated references. the latest edition of the referenced document (including any amendments) applies.
EN 50173-1:2018, Information technology — Generic cabling systems — Part 1: General requirements
EN 50174-1, Information technology — Cabling installation — Part 1: Installation specification and quality assurance
EN 50174-2, Information technology — Cabling installation — Part 2: Installation planning and practices inside buildings
EN 501 74-3, In formation technology — Cabling installation — Part 3: Installation planning and practices outside buildings
EN 61076-3-106:2006. Connectors for electronic equipment — Product requirements — Part 3-106:
Rectangular connectors — Detail specification for protective housings for use with 8-way shielded and
unshielded connectors for industrial environments incorporating the IEC 60603-7 series interface (IEC 6 1076-
3-106:2006)
EN 61076-3-110, Connectors for electronic equipment — Product requirements — Part 3-110: Detail specification for shielded, free and fixed connectors for data transmission with frequencies up to 1 000 MHz
(IEC 61076-3-110)
EN 61754-7-1, Fibre optic interconnecting devices and passive components — Fibre optic connector interfaces — Part 7-1: Type MPO connector family — One fibre row (IEC 61754-7-1)
EN IEC 61754-7-2, Fibre optic interconnecting devices and passive components — fibre optic connector interfaces — Part 7-2: Type MPO connector family — Two fibre rows (IEC 61754-7-2)
EN 61754-20:2012, Fibre optic interconnecting devices and passive components — Fibre optic connector interfaces — Part 20: Type LC connector family (lEG 61754 20:2012)
3 Terms, definitions and abbreviations
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 50173-1 and EN 50174-1 and the following apply.
3.1.1
computer room space
area within the data centre that accommodates the data processing, data storage and telecommunication equipment that provides the primary function of the data centre.
3.1.2
data centre
structure, or group of structures, dedicated to the centralized accommodation, interconnection and operation of information technology and network telecommunications equipment providing data storage, processing and transport services together with all the facilities and infrastructures for power distribution and environmental control together with the necessary levels of resilience and security required to provide the desired service availability
Note Ito entry: A structure can consist of multiple buildings andlor spaces with specific functions to support the pnmary (unction.
Note 2 to entry: The boundaries of the structure or space considered the data centre wbich includes the infomiation and communication technology equipment and supporting environmental controls can be defined within a larger structure or building.
[SOURCE: EN 50600-1:2012. 3.1.9. modified — added Note 2 to entryl
3.1.3
equipment outlet
fixed connecting device where the zone distribution cabling terminates and providing the interface to the equipment cabling
3.1.4
Intermediate distribution cable
cable connecting the intermediate distributor to the zone distributor
3.1.5
Intermediate distributor
distributor used to make connections between the main distribution cabling subsystem, intermediate distribution cabling subsystem, network access cabling subsystem and active equipment
3.1.6
local distribution point
connection point in the zone distribution cabling subsystem between a zone distributor and one or more equipment outlets
3.1.7
local distribution point cable LDP cable
cab’e connecting a local distribution point to an equipment outlet
4.4.1.2 Intermediate distribution cabling subsystem
The intermediate distribution cabling subsystem extends from an ID to the ZDs connected to it. The subsystem includes:
a) the intermediate distribution cables;
b) the mechanical termination of the intermediate distribution cables at the ID together with associated patch cords and/or jumpers at the ID:
c) the mechanical termination of the intermediate cables at the ZD.
Although equipment cords are used to connect the transmission equipment to the cabling subsystem, they are not considered part of the intermediate distribution cabling subsystem because they can be application- specific.
4.4.1.3 Main distribution cabling subsystem
The main distribution cabling subsystem extends from an MD to the IDs connected to it. The subsystem includes:
a) the main distribution cables;
b) the mechanical termination of the main distribution cables at the MD together with associated patch cords and/or jumpers at the MD:
c) the mechanical termination of the main distribution cables at the ID.
Although equipment cords are used to connect the transmission equipment to the cabling subsystem, they are not considered part of the main distribution cabling subsystem because they can beapplication-specific.
4.4.1.4 Network access cablIng subsystem
The network access cabling subsystem extends from an MD, ID or ZD to the ENIs and/or other distributors of the EN 50173 series connected to it. The subsystem includes:
a) the network access cables;
b) the mechanical termination of the network access cables at the ENI;
c) the mechanical termination of the network access cables at the MD, ID, ZO or other distributors of the EN 50173 series.
Although equipment cords are used to connect the transmission equipment to the cabling subsystem, they are not considered part of the network access cabling subsystem because they can be application-specific.BS/EN 50173-5-2018 pdf download.

                                           Related Information                                             Download
PS:Thank you for your support!
BS EN 12607-3-2000 pdf download BS Standards

BS EN 12607-3-2000 pdf download

BS EN 12607-3-2000 pdf download.Methods of test for petroleum and its products — BS 2000-460.3: Bitumen and bituminous binders — Determination of the resistance to hardening under the influence of heat and air — Part 3: RFT...
Read More
EN 12329-2000 pdf download BS Standards

EN 12329-2000 pdf download

BS EN 12329-2000 pdf download.Corrosion protection of metals — Electrodeposited coatings of zinc with supplementary treatment on iron or steel. This BS EN 12329 specifies requirements for electrodeposited coatings of zinc on iron or steel witt supplementary...
Read More
BS EN 1430-2000 pdf download BS Standards

BS EN 1430-2000 pdf download

BS EN 1430-2000 pdf download.Methods of test for petroleum and its products — BS 2000-292:Bitumen and bituminous binders — Determination of particle polarity of bitumen emulsions (Identical with IP 292-2000). This BS EN 1430 specifies a method...
Read More

LEAVE A REPLY

Anonymous netizen Fill in information