BS/EN 14511-2-2018 pdf download.Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors Part 2: Test conditions.
chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. The standard also specifies the test conditions for the rating of air-cooled and water(brine)-cooled process chillers.
1.3 This European Standard specifies the conditions for which performance data is to be declared for single duct and double duct units for compliance to the Ecodesign Regulation 206/2012 and Energy Labelling Regulation 626/2011.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
EN 14511-1:2018, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers with electrically driven compressors – Part 1: Terms and definitions
EN 14511-4:2018, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors- Part 4: Requirements
EN 15218, Air conditioners and liquid chilling packages with evaporatively cooled condenser and with electrically driven compressors for space cooling — Terms, definitions, test conditions, test methods and requirements
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1451 1-1:2OJi apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
• IEC Electropedia: available at http:llwwwelectropedia.orgi
• ISO Online browsing platform: available at http://www.iso.org/obp
4 Test conditions
4,1 Environmental conditions and electrical power supply requirements
The tests shall be carried out under the environmental conditions specified in Table 1 or Table 2 depending on the location of the unit.
For all units, electrical power voltage and frequency shall be given by the manufacturer.
4.2 Rating conditions
For the rating tests, the appropriate test conditions shall be applied in accordance with:
— Table 3 for air-to-air units in heating mode;
— Table 4 for air-to-air units in cooling mode;
— Table 5 for water(brine)-to-air units in heating mode;
— Table 6 for water(brine).to-air units in cooling mode;
— Tables 7 to 10 for water(brine)-to-water(brine) units in heating mode, depending on the temperature applications;
— Table 11 for water(brine)-to-water(brine) units in cooling mode;
— Tables 12 to 15 for air-to-water(brine) in heating mode, depending on the temperature applications;
— Table 16 for air-to-water(brine) units in cooling mode;
— Table 17 for liquid chilling packages with remote condenser:
— Table 18 for liquid chilling packages for heat recovery condenser:
— Table 19 for air-cooled multisplit systems and modular air-cooled multisplit systems in the heating mode;
— Table 20 for air-cooled multisplit systems and modular air-cooled multisplit systems in the cooling mode;
— LabIei for modular heat recovery air-cooled multisplit systems;
— Table 22 for water-cooled multisplit systems and modular water-cooled multisplit systems in the heating mode;
— Table 23 for water-cooled multisplit systems and modular water-cooled multisplit systems in the cooling mode:
— Table 24 for modular heat recovery water-cooled multisplit systems.
— Table 25 for process chillers
For units with brine, the test shall be carried out with the brine specified by the manufacturer, see EN 145114:2018, 7,2.1.
For air-to-water(brine),and water(brine)-to-water(brine) heat pumps, the manufacturer may declare the water(brine) temperatures levels (low, intermediate, medium, and high) applicable to the heating mode.
NOTE For comparison purposes between reverse cycle and non-reverse cycle units, the conditions on the water(brine) side are given by the inlet and outlet water(brinc) temperatures, possibly leading to different water(brine) how rates in heating and cooling modes.
The rating tests in heating mode also apply for units having evaporatively cooled condenser, which performance in cooling mode is determined in accordance with EN 15218, and which can operate in heating mode.
The standard rating conditions, extracted from Table 3 for heating mode and specified in Table ZA.1, shall be used to determine the rated capacity (Prated), the rated power input (Pcop), the rated coefficient of performance (COPraiecj) and the electricity consumption (Qoo. QSD) in heating mode.BS/EN 14511-2-2018 pdf download.

                                           Related Information                                             Download
PS:Thank you for your support!
BS EN 12607-3-2000 pdf download BS Standards

BS EN 12607-3-2000 pdf download

BS EN 12607-3-2000 pdf download.Methods of test for petroleum and its products — BS 2000-460.3: Bitumen and bituminous binders — Determination of the resistance to hardening under the influence of heat and air — Part 3: RFT...
Read More
EN 12329-2000 pdf download BS Standards

EN 12329-2000 pdf download

BS EN 12329-2000 pdf download.Corrosion protection of metals — Electrodeposited coatings of zinc with supplementary treatment on iron or steel. This BS EN 12329 specifies requirements for electrodeposited coatings of zinc on iron or steel witt supplementary...
Read More
BS EN 1430-2000 pdf download BS Standards

BS EN 1430-2000 pdf download

BS EN 1430-2000 pdf download.Methods of test for petroleum and its products — BS 2000-292:Bitumen and bituminous binders — Determination of particle polarity of bitumen emulsions (Identical with IP 292-2000). This BS EN 1430 specifies a method...
Read More

LEAVE A REPLY

Anonymous netizen Fill in information