ASME A90.1:2003 pdf download SAFETY STANDARD FOR BELT M AIiILIFTS
rated speed: the speed of the belt at which the manlift isdesigned to run (refer to para. 5.4).
safety stop device: any electrical or electromechanicaldevice (such as a limit switch, photoelectric eye, or proximity probe) that shall cause the electric power to beremoved from the driving machine motor and brakestopping the manlift.
severe belt damage: the protective outer cover of a belt thabecomes cut, cracked, or separated, exposing damagedinner fabric, and such damage that extends across thefull width of the belt or spans between adjacent boltholes. A torn belt is also considered severe.
split-rail safety stop: an electric limit switch operatedmechanically by the rollers on the manlift steps.step (platform): a passenger carrying unit.superficial belt cover damage: the protective outer coverof a belt that becomes scratched, cut, or crackedexposing the inner fabric. Such damage is not continuousacross the full width of the belt.
torn: a severence of any length or width that goesthrough the entire thickness of the belt.
GENERAL REQUIREMENTS
4.1 Floor Openings
4.1.1 Allowable Size. New installations shall haveminimum floor openings of 30 in.(760 mm) and maximum floor openings of 36 in. (915 mm) Floor openingwidths for both the up- and down-runs for existinginstallations shall be in accordance with Table 1 andFig.1.
4.1.2 Uniformity. All floor openings for a given man-lift shall be uniform in size and shall be approximatelycircular, and each shall be located vertically above theopening below it.
4.2 Riding Clearance
(a) There shall be no encroachment of any kind withinthe cylindrical space defined by the outer edges of the floor openings for the entire run of the manlift(b) Should maintenance or construction work beplanned for in close proximity to the manlift causing anencroachment on the space defined in para. 4.2(a), themanlift shall be shut down during such work.
4.3 Landings
4.3.1 Vertical Clearance. The clearance between thefloor or mounting platform and the lower edge for theunderfloor hood above it required by para. 4.4 shall benot less than 7 ft 6 in.(2 285 mm). Where this clearancecannot be obtained, no access to the manlift shall beprovided, and the manlift runway shall be enclosedwhere it passes through such floor. The enclosure shallbe equipped with an emergency exit.
4.3.2 Clear Landing Space. The landing space adjacent to the floor openings shall be free from obstructionand kept clear at all times. The landing space shall beat least 2 ft (610 mm) in width from the edge of the flooropening used for mounting and dismounting (see Figs2 and 3).
4.3.3 Lighting of Landings. Adequate lighting, notless than 5 fc (54 1x), shall be provided at each floorlanding at all times when the lift is in operation.
4.3.4 Landing Surface. The landing surface at theentrances and exits to the manlift shall be constructedand maintained to provide safe footing at all times.
4.3.5 Emergency Landings. Where there is a travel of50 ft (15 m) or more between floor landings, one or moreemergency landing(s) shall be provided so that there isa landing (either floor or emergency) for every 25 ft (7.5m) or less of manlift travel.
(a) Emergency landings shall be accessible from boththe up- and down-runs of the manlift and shall giveaccess to the ladder as required in para. 4.8.
(b) Emergency landings shall be provided with stan-dard railings and toeboards.
(c) Platforms constructed to give access to bucket elevators or other equipment for the purpose of inspection,lubrication, and repair may also serve as emergencylandings under this paragraph. All such platforms shallthen be considered part of the emergency landing andprovided with standard railings and toeboards.

                                           Related Information                                             Download
PS:Thank you for your support!
ASME B107.100:2002 pdf download ASME Standards

ASME B107.100:2002 pdf download

ASME B107.100:2002 pdf download WKENGHLD INCORPORATING ASME B107.6, ASME B107.9, ASME B107.39, and ASME B107.40 4.5 Proof Torque When tested as specified, wrenches shall withstand the proof torque specified in the applicable tables without failure or permanent...
Read More
ASME BPE:2002 pdf download ASME Standards

ASME BPE:2002 pdf download

ASME BPE:2002 pdf download BIOPROCESSING EOUIPMENT GR-1 INTRODUCTION This Standard provides the requirements applicableto the design of bioprocessing equipment inciudingaspects related to sterilily and cleanability,dimensionsand tolcranccs, surfacc finish, material joining, andscals. Thcsc apply to: (a) componcnts that...
Read More
ASME N509:2002 pdf download ASME Standards

ASME N509:2002 pdf download

ASME N509:2002 pdf download NUCLEAR POWER PLANT UNITS AID CDMPONENTS 1 SCOPE This Standard covers requirements for the designconstruction, and qualification and acceptance testingof the air-cleaning units and components which makeup Engineered Safety Feature (ESF) and other...
Read More

LEAVE A REPLY

Anonymous netizen Fill in information