8.1 Operating Requirements. To comply with this standard, any production unit shall meet the minimum operating requirements detailed in this section. 8.2 Water-Trace Test. Self-Contained Humidifiers shall pass a water-trace test for each class designation as specified in the manufacturer’s installation instructions when operated at Standard Rating Conditions specified in 6.2. 8.2.1 Procedure. The Self-Contained Humidifier shall operate for the duration of the Standard Rating test.
8.2.2 Requirements.
8.2.2.1 During the test, water shall not drip or run off the Self-Contained Humidifier under test.
8.2.2.2 After the test, the surface under or surrounding the Self-Contained Humidifier shall be dry, provided that the surface temperature exceeds 42°F [5.6°C].
8.3 Water Flow Control Test. Self-Contained Humidifiers shall pass the following water flow control test when operated at Standard Rating Conditions specified in 6.2 except for water pressure conditions.
8.3.1 Water Pressure Conditions. Water pressure conditions shall be maintained at 20 psi [140 kPa].
8.3.2 Procedure. The Self-Contained Humidifier shall operate continuously for 30 minutes. The water pressure shall then be raised to 125 psi [862 kPa] and the Self-Contained Humidifier shall then operate continuously for an additional 30 minutes. Operation and resetting of the water control valve prior to establishment of continuous operation shall be permitted.
8.3.3 Requirements. During the test there shall be no dripping or run-off of water from the Self-Contained Humidifier. Section 9. Marking and Nameplate Data 9.1 Marking and Nameplate Data. As a minimum, the nameplate shall display the manufacturer’s name, model designation, and electrical characteristics. Nameplate voltages for 60 Hz systems shall include one or more of the equipment nameplate voltage ratings shown in Table 1 of ARI Standard 110. Nameplate voltages for 50 Hz systems shall include one or more of the utilization voltages shown in Table 1 of International Standard IEC 60038. Section 10. Conformance Conditions
10.1 Conformance. While conformance with this standard is voluntary, conformance shall not be claimed or implied for products or equipment within the standard’s Purpose (Section 1) and Scope (Section 2) unless such product claims meet all of the requirements of the standard and all of the testing and rating requirements are measured and reported in complete compliance with the standard. Any product that has not met all the requirements of the standard shall not reference, state, or acknowledge the standard in any written, oral, or electronic communication.