BS 7671:2018/A1:2020 pdf free download – Requirements for Electrical Installations – IET Wiring Regulations.
The particular requirements for each section (special installation or location)in Part 7 supplement or modify the general requirements contained in other parts of BS 7671.
The absence of reference to the exclusion of a part, a chapter, a section or a regulation means that the correspondin general regulations are applicable.
thin Parts 1 to 6. The numbering does not, therefore, necessarily follow sequentially and new numbers have been dded as required. Numbering of figures and tables takes the number of the section followed by a sequential number.
The particular requirements of this section apply to circuits intended to supply electric vehicles for charging purposes.
The requirements of this section do not apply to electric vehicle charging points that:
(i)employ inductive charging;
(ii)charge mobility scooters and similar vehicles of 10 A and less;
The protective measures of obstacles and placing out of reach (Section 417) shall not be used;
The protective measures of non-conducting location(Regulation418.1)and earth-free local equipotential bonding (Regulation 418. 2 ) shall not be used;